Plan Review Notes
Plan Review Notes For Permit 16111261
Permit Number 16111261
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-12 14:51:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. S0.1, EXPLAIN VELOCITY HEIGHT OF 20FT FOR RESIDENT
 BUILDINGS. IS THIS THE MEAN ROOF HEIGHT? THIS IS A FOUR
 STORY BUILDING. REVISE OR CLARIFY, FBC 107. IT IS NOT
 CLEAR WHY THE CLUBHOUSE PRESSURES, INCLUDING ROOF
 PRESSURES, ARE IN SOME CASES HIGHER THAN THE RESIDENT
 BUILDINGS (OR VERY CLOSE TO THE SAME), BUT THE
 CLUBHOUSE IS ONE STORY, PITCHED ROOF; RESIDENT
 BUILDINGS ARE FOUR STORIES, FLAT ROOF.
  
 2. SPECIFY SOFFIT PRESSURES, FBC 1609.
  
 3. KAYKAN SOFFIT PRODUCT APPROVAL, INDICATE WHICH
 PRODUCT AND INSTALLATION METHOD IS PROPOSED (DRAWING
 PAGE 1 OF 15).
  
 4. MULE HIDE SINGLE PLY ROOF PRODUCT APPROVAL WAS
 SUBMITTED. THE ASSEMBLY PROPOSED WAS NOT INDICATED.
  
 IF THIS INFORMATION IS NOT PROVIDED, THIS INFORMATION
 WILL BE REQUIRED AT TIME OF ROOF SUB PERMIT
 APPLICATION, FBC 1609.
  
 5. WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB, FBC 105.
  
 6. PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT
 ACOUSTIC INSULATION:
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 720.2 OR 603.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723 (FLAME SPREAD).
  
 7. BUILDING TYPE (SHEET G0.1) IS IIIB. REVISE PLAN TO
 INCLUDE THE FLOOR CEILING ASSEMBLY; THIS INFORMATION IS
 REQUIRED TO DETERMINE COMPLIANCE FOR THE FLOORING
 UNDERLAYMENT SELECTED.
  
 8. FBC A 604.5.2, THE REAR GRAB BAR IS TO EXTEND 12 IN
 ONE DIRECTION AND 24 INCHES IN THE OTHER DIRECTION
 (TRANSFER SIDE); SEE DETAIL 1 A 5.4, DETAIL DEPICTS THE
 GRAB BAR CENTERED. REVISE ALL AFFECTED DETAILS AND
 PLANS.
  
 9. FBC EC CHAPTER 2 DEFINITIONS, SEE DEFINITION OF
 RESIDENTIAL BUILDING (THREE STORIES OR LESS); PROVIDE
 COMMERCIAL BUILDING ENERGY CALCS, FBC EC C103.
  
 10. FBC EB, PROVIDE INFORMATION AS TO HOW IT WAS
 DETERMINED THAT THIS IS A LEVEL II ALTERATION (RATHER
 THAN A LEVEL III). PLEASE SEND THIS INFORMATION VIA
 EMAIL FOR PRELIMINARY REVIEW PRIOR TO RESUBMITTAL.
  
  
  