2016-12-07 10:44:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111259
 12/7/16
  
 1) SHEET M1.1: PROVIDE THE EFFICIENCY RATING OF THE
 10-TON UNIT IN THE SCHEDULE.
  
 2) SUBMIT AN AC CHANGEOUT FORMS FOR THE REPLACED
 SYSTEM. THE FORM CAN BE FOUND ON THE DEVELOPMENT
 SERVICES WEBSITE- WWW.CITYOFWPB.COM.
  
 3) ENERGYGAUGE COMPLIANCE FORM: A) CORRECT THE SYSTEM
 NUMBER TO SYSTEM 4 TO MATCH THE PLANS. B) COMPLETE THE
 MANDATORY REQUIREMENTS CHECKLIST ON PAGE 7.
  
 4) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 ANCHORING THE NEW CU.
  