| 2017-03-28 15:34:36 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16111255 | | | 3/28/17 | | | | | | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, THE AC | | | COOLING AND HEATING CALCULATIONS REQUIRE AN ENGINEER'S | | | SIGNATURE AND SEAL- SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. PLEASE NOTE THAT THE AC SUMMARY | | | CALCULATIONS THAT HAVE BEEN PREPARED BY GREG CHEROK, | | | ARE SEPARATE DOCUMENTS FROM THE ENERGYGAUGE COMPLIANCE | | | SUBMITTAL. | | | | | | 2) SHEET M2: PROVIDE AN APPROVED SUBMITTAL FOR THE | | | SEISMIC BRACKETS THAT ARE CONNECTING THE RTU TO THE | | | CURB. PLEASE NOTE THAT ANCHORAGE OF ROOFTOP MECHANICAL | | | IS TO BE DESIGNED IN ACCORDANCE WITH SECTION 1609 WIND | | | LOADS FBC-14 BUILDING. THIS PROJECT IS NOT IN A SEISMIC | | | ZONE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|