2017-03-28 15:34:362ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16111255
 3/28/17
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, THE AC
 COOLING AND HEATING CALCULATIONS REQUIRE AN ENGINEER'S
 SIGNATURE AND SEAL- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION. PLEASE NOTE THAT THE AC SUMMARY
 CALCULATIONS THAT HAVE BEEN PREPARED BY GREG CHEROK,
 ARE SEPARATE DOCUMENTS FROM THE ENERGYGAUGE COMPLIANCE
 SUBMITTAL.
  
 2) SHEET M2: PROVIDE AN APPROVED SUBMITTAL FOR THE
 SEISMIC BRACKETS THAT ARE CONNECTING THE RTU TO THE
 CURB. PLEASE NOTE THAT ANCHORAGE OF ROOFTOP MECHANICAL
 IS TO BE DESIGNED IN ACCORDANCE WITH SECTION 1609 WIND
 LOADS FBC-14 BUILDING. THIS PROJECT IS NOT IN A SEISMIC
 ZONE.
  