2016-12-08 14:33:051ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #1611255
 12/8/16
  
 1) CORRECT THE ENERGYGAUGE FORM TO SHOW THE CORRECT
 DATA FOR THE 4-TON HEAT PUMP SYSTEM. THE FORM IS
 INDICATING IT TO BE A10-TON SYSTEM.
  
 2) THE HEAT PUMP COOLING AND HEATING CALCULATIONS MUST
 BEAR THE SIGNATURE AND SEAL OF THE ENGINEER OF RECORD-
 SECTION C403.2.1 FBC-14 FBC-14 ENERGY CONSERVATION.
  
 3) COMMISSIONING IS REQUIRED IN ACCORDANCE WITH SECTION
 C408.1 FBC-14. PLEASE SUBMIT A COMMISSIONING PLAN OR
 PROVIDE AN OUTLINE ON THE PLAN DETAILING THE
 PROCEDURES. PLEASE NOTE THAT FINAL CO OF THE PROJECT IS
 CONTINGENT ON SUBMITTAL OF THE FINAL COMMISSIONING
 REPORT TO THE BUILDING OWNER
  
 4) DEMAND CONTROLLED VENTILATION IS REQUIRED PER
 SECTION C403.2.5.1. THE PLAN IS INDICATING ONLY RTU-4
 TO BE IN COMPLIANCE.
  
 5) PLEASE PROVIDE A SUBMITTAL FOR THE CO SENSOR WITH AN
 APPROVAL STAMP BY THE EOR.
  
 6) PROVIDE COMPLETE ENGINEERING FOR INSTALLATION OF THE
 RTU'S INCLUDING THE WIND DESIGN CRITERIA, AND
 ATTACHMENT AND FASTENING DETAILS- SECTION 301.15.
  
 7) SHOW THE LOCATION(S) OF THE UNIT HEATER ON THE
 PLANS.
  