| Plan Review Notes For Permit 16111255 |
| Permit Number |
16111255 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-13 13:40:16 | 16111255 | | | 2025 OKEECHOBEE BLVD. | | | WEST PALM BEACH | | | COMMERCIAL INTERIOR | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE INTERIOR LIGHTING DETAIL/CALCULATION VERIFYING | | | COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY | | | CONSERVATION REQUIREMENTS. FBC C405 | | | | | | VERIFY THERE ARE GFCI PROTECTED RECEPTACLES LOCATED ON | | | THE ROOF TOP FOR SERVICING THE AIR CONDITIONING | | | EQUIPMENT. NEC 210.8, 210.63 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-373-3701 | | | [email protected] | | | |
|