| Plan Review Notes For Permit 16111241 |
| Permit Number |
16111241 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-09 08:41:08 | | | | BUILDING PROVISO: ROOFTOP EQUIPMENT ON STANDS TO COMPLY | | | WITH: | | | 2014 FBC-B TABLE 1509.6.5. WHERE ROOFING MATERIALS | | | EXTEND | | | BENEATH THE UNIT, ON RAISED EQUIPMENT SUPORTS PROVIDING | | | A | | | MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE | | | 1509.6.5. | | | THE SUPPORTS PROVIDING CLEARANCE ARE THE HORIZONTAL | | | SUPPORTS, | | | THE VERTICAL DIMENSION SHOULD BE TAKEN FROM THE BOTTOM | | | OF THE | | | HORIZONTAL SUPPORTS TO THE FINISH ROOF DECK. IF THE | | | HEATER IS | | | BETWEEN 36-48 INCHES THEN THE CLEAR HEIGHT MINIMUM | | | SHALL BE | | | 24 INCHES HIGH. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | |
|