| Plan Review Notes For Permit 16111231 |
| Permit Number |
16111231 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-01 16:48:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE NO EQUIPMENT SPECS PROVIDED WITH THIS | | | SUMITTAL, BOTH FOR THE FUEL TANK AND THE GENERATOR. | | | | | | PLEASE PROVIDE THE SPECS FOR EACH, INCLUDE WHAT TYPE OF | | | FUEL AND HOW IT WILL BE PROTECTED FROM VEHICLE IMPACT. | | | | | | | | | | | | 2) HOW WILL THE POWER BE ACCESSED, A CABLE CROSS OVER | | | IS INDICATED. IS THAT GROUND CABLEING, EXTENSION CORDS, | | | OVERHEAD WIRES, ETC. | | | | | | HOW WILL THESE POWER LINES BE SUPPORTED AND/OR | | | PROTECTED FROM PEDESTRIAN OR CONSTRUCTION EQUIPMENT | | | IMPACT? | | | | | | WILL THE CONNECTIONS TO THE BUILDING BE TO PERMANENTLY | | | INSTALLED ELECTRICAL EQUIPMENT OR TEMPORARY ? | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|