2016-12-01 16:48:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO EQUIPMENT SPECS PROVIDED WITH THIS
 SUMITTAL, BOTH FOR THE FUEL TANK AND THE GENERATOR.
  
 PLEASE PROVIDE THE SPECS FOR EACH, INCLUDE WHAT TYPE OF
 FUEL AND HOW IT WILL BE PROTECTED FROM VEHICLE IMPACT.
  
  
  
 2) HOW WILL THE POWER BE ACCESSED, A CABLE CROSS OVER
 IS INDICATED. IS THAT GROUND CABLEING, EXTENSION CORDS,
 OVERHEAD WIRES, ETC.
  
 HOW WILL THESE POWER LINES BE SUPPORTED AND/OR
 PROTECTED FROM PEDESTRIAN OR CONSTRUCTION EQUIPMENT
 IMPACT?
  
 WILL THE CONNECTIONS TO THE BUILDING BE TO PERMANENTLY
 INSTALLED ELECTRICAL EQUIPMENT OR TEMPORARY ?
  
 PLEASE PROVIDE DETAILS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL