| Plan Review Notes For Permit 16111229 |
| Permit Number |
16111229 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-03 02:50:49 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | | ADDED BREAKROOM SINK, THE DRINKING FOUNTAIN AND THE MOP | | | SINK.WPB AMEND. TO FBC SEC. 107.3.5.3. | | | 2) THE BREAKROOM SINK SHALL COMPLY WITH THE 2014 | | | FBC-ACCESS. SECS.212.1, 212.3, 606. | | | 3) HOT WATER IS REQUIRED AT THE UTILITY SINK AND THE | | | BREAKROOM SINK PER THE 2014 FBC - PLUMBING SEC.607.1 | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|