Plan Review Notes
Plan Review Notes For Permit 16111227
Permit Number 16111227
Review Stop B
Sequence Number 2
Notes
Date Text
2016-12-08 07:33:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE CITY OF WEST PALM BEACH HAS NOT ADOPTED RAS 150.
  
 1) FBC 107.3.4 - THE GAF BUR ROOFING ASSEMBLY SYSTEM
 THAT WAS SELECTED ON PAGE 14 OF NOA NO.13-1022.15 HAS A
 MAXIMUM DESIGN PRESSURE OF -45 PSF. ENHANCED FASTENING
 IS REQUIRED TO MEET THE HIGHER PRESSURES AT THE
 PERIMETER AND CORNER AREAS OF THE ROOF. LIMITATION
 NUMBER 7 ON PAGE 16 OF THE PRODUCT APPROVAL ALLOWS THIS
 TO BE DONE USING RAS 117 CALCULATIONS. LIMITATION
 REQUIRES THE RAS 117 CALCULATIONS TO BE SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF CONSULTANT.
 SUBMIT TWO (2) SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS.
  
  