| Plan Review Notes For Permit 16111227 |
| Permit Number |
16111227 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-08 07:33:58 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THE CITY OF WEST PALM BEACH HAS NOT ADOPTED RAS 150. | | | | | | 1) FBC 107.3.4 - THE GAF BUR ROOFING ASSEMBLY SYSTEM | | | THAT WAS SELECTED ON PAGE 14 OF NOA NO.13-1022.15 HAS A | | | MAXIMUM DESIGN PRESSURE OF -45 PSF. ENHANCED FASTENING | | | IS REQUIRED TO MEET THE HIGHER PRESSURES AT THE | | | PERIMETER AND CORNER AREAS OF THE ROOF. LIMITATION | | | NUMBER 7 ON PAGE 16 OF THE PRODUCT APPROVAL ALLOWS THIS | | | TO BE DONE USING RAS 117 CALCULATIONS. LIMITATION | | | REQUIRES THE RAS 117 CALCULATIONS TO BE SIGNED AND | | | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, | | | REGISTERED ARCHITECT OR REGISTERED ROOF CONSULTANT. | | | SUBMIT TWO (2) SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS. | | | | | | |
|