| 2017-01-09 18:04:41 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | (1) PROVIDE PLANS AS PER (CITY OF WEST PALM BEACH LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE (FBC) 2010 |
| | CHAPTER 1 ADMINISTRATION107.2.1.4) |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES |
| | PROVIDE COMPANY NAME, QUALIFIER NAME, CONTRACTOR |
| | LICENSE #, ADDRESS OF JOB SITE |
| | |
| | (2) PROVIDE EQUIPMENT SCHEDULE ON PLANS (R403.6.1) |
| | (3) PROVIDE RETURN AIR FROM BEDROOMS (AS PER FBC 2014 - |
| | M1602.4 BALANCED RETURN AIR) |
| | (4) PROVIDE EXHAUST IN ALL BATHROOMS (AS PER FBC 2014) |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |