2017-01-31 16:33:562ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16111217
 1/31/17
  
 1) M2.0: IT APPEARS FROM THE DRAWING THAT INADEQUATE
 MAKEUP AIR IS BEING PROVIDED FOR THE MEDICAL WASTE ROOM
 EXHAUST. REFER TO SECTION 601.2 EXCEPTION 1 AND PROVIDE
 A CALCULATION USING THE CFMS OF O/A BEING PROVIDED TO
 CORRIDOR 120.
  
 2) M2.0: PLEASE INDICATE THE EXACT DISCHARGE LOCATION
 OF THE FC-1 CONDENSATE DRAINAGE PIPING. PLEASE NOTE
 THAT IT SHALL NOT DRAIN INTO THE CITY SANITARY SYSTEM
 PER SECTION 90-126 CITY OF WEST PALM BEACH CODE OF
 ORDINANCES.
  
 3) M2.1: 2ND REQUEST FOR THE WIND LOAD DESIGN CRITERIA
 FOR INSTALLATION OF THE ROOFTOP STAND AND CONDENSER
 UNIT- SEE SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER