| 2017-02-08 12:46:39 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: CONTINENTAL DIALYSIS CARE CENTER RENO. |
| | JOB ADDRESS: 2000 CONTINENTAL DRIVE |
| | DESCRIPTION: ADD 15 DIALYSIS TREATMENT STATIONS TO |
| | EXISTING AS PER PERMIT |
| | MASTER PERMIT: 16111217 |
| | |
| | BELOW PLEASE FIND A RESPONSE TO YOUR CORRECTIONS AS |
| | PRESENTED AND ADDITIONAL ITEMS PREVIOUSLY OVERLOOKED BY |
| | THE REVIEWER. ADDITIONAL CORRECTIONS MAY BE REQUIRED |
| | AFTER REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WHEN YOU RESUBMIT, PLEASE REARRANGE THE PLANS SO |
| | THAT THE NEW ?T? SHEET APPEARS AT THE BEGINNING RATHER |
| | THAN MIXED IN THE PLAN SET. |
| | 2. YOUR NOTE TO THE CODE REFERENCE DOES NOT NECESSARILY |
| | MEET THE REQUIREMENTS. YOU NEED TO SHOW THE ACTUAL |
| | WIREWAY SIZE ON THE PLANS. AN ERROR HERE CAN BE A VERY |
| | COSTLY REPAIR. |
| | 3. PROVIDE THE DISTANCE OF ALL THE SERVICES (UTILITY & |
| | GENERATOR) TO DETERMINE COMPLIANCE WITH THE VOLTAGE |
| | DROP REQUIREMENTS OF THE FBC-EC405.7.3. |
| | 4. WHEN YOU FACTOR IN THE REQUIRED ADJUSTMENTS FOR NEC |
| | 310.15(B)(3)(A) FOR MORE THAN THREE CURRENT CARRYING |
| | CONDUCTORS INSIDE THE RACEWAY AND THE CORRECTION PER |
| | NEC 310.15(B)(2)(A) FOR THE ABOVE GROUND RACEWAYS |
| | EXPOSED TO DIRECT SUNLIGHT THE SPECIFIED CONDUCTORS ARE |
| | NOT ADEQUATE TO CARRY THE PROJECTED LOAD. |
| | 5. THE PROVIDED RISER DIAGRAM IS CONFUSING WHEN |
| | REFERRING TO THE PROPOSED RACEWAY PROPERTIES, YOU |
| | INDICATE PVC AND ON THE SAME DESCRIPTION YOU STATE RMC. |
| | 6. YOU SHALL PROVIDE MANUFACTURER SPECS FOR THE |
| | PROPOSED GENERATOR (THE GENERATOR REQUIRES A SEPARATE |
| | PERMIT AND SUBMITTAL PACKAGE). |
| | 7. WHEN SUBMITTING THE CORRECTION HEREIN MENTIONED, |
| | PLEASE INCLUDE THE NOTE PER NEC 110.16 FOR THE |
| | ARC-FLASH WARNING. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |