Plan Review Notes
Plan Review Notes For Permit 16111217
Permit Number 16111217
Review Stop E
Sequence Number 2
Notes
Date Text
2017-02-08 12:46:39ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: CONTINENTAL DIALYSIS CARE CENTER RENO.
 JOB ADDRESS: 2000 CONTINENTAL DRIVE
 DESCRIPTION: ADD 15 DIALYSIS TREATMENT STATIONS TO
 EXISTING AS PER PERMIT
 MASTER PERMIT: 16111217
  
 BELOW PLEASE FIND A RESPONSE TO YOUR CORRECTIONS AS
 PRESENTED AND ADDITIONAL ITEMS PREVIOUSLY OVERLOOKED BY
 THE REVIEWER. ADDITIONAL CORRECTIONS MAY BE REQUIRED
 AFTER REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WHEN YOU RESUBMIT, PLEASE REARRANGE THE PLANS SO
 THAT THE NEW ?T? SHEET APPEARS AT THE BEGINNING RATHER
 THAN MIXED IN THE PLAN SET.
 2. YOUR NOTE TO THE CODE REFERENCE DOES NOT NECESSARILY
 MEET THE REQUIREMENTS. YOU NEED TO SHOW THE ACTUAL
 WIREWAY SIZE ON THE PLANS. AN ERROR HERE CAN BE A VERY
 COSTLY REPAIR.
 3. PROVIDE THE DISTANCE OF ALL THE SERVICES (UTILITY &
 GENERATOR) TO DETERMINE COMPLIANCE WITH THE VOLTAGE
 DROP REQUIREMENTS OF THE FBC-EC405.7.3.
 4. WHEN YOU FACTOR IN THE REQUIRED ADJUSTMENTS FOR NEC
 310.15(B)(3)(A) FOR MORE THAN THREE CURRENT CARRYING
 CONDUCTORS INSIDE THE RACEWAY AND THE CORRECTION PER
 NEC 310.15(B)(2)(A) FOR THE ABOVE GROUND RACEWAYS
 EXPOSED TO DIRECT SUNLIGHT THE SPECIFIED CONDUCTORS ARE
 NOT ADEQUATE TO CARRY THE PROJECTED LOAD.
 5. THE PROVIDED RISER DIAGRAM IS CONFUSING WHEN
 REFERRING TO THE PROPOSED RACEWAY PROPERTIES, YOU
 INDICATE PVC AND ON THE SAME DESCRIPTION YOU STATE RMC.
 6. YOU SHALL PROVIDE MANUFACTURER SPECS FOR THE
 PROPOSED GENERATOR (THE GENERATOR REQUIRES A SEPARATE
 PERMIT AND SUBMITTAL PACKAGE).
 7. WHEN SUBMITTING THE CORRECTION HEREIN MENTIONED,
 PLEASE INCLUDE THE NOTE PER NEC 110.16 FOR THE
 ARC-FLASH WARNING.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  