Plan Review Notes
Plan Review Notes For Permit 16111217
Permit Number 16111217
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-09 12:13:251ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS TO BE MEASURE FROM FINISHED FLOOR TO TOP
 OF GRIPPING SURFACE. PER FBC PL 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 2.TWO WATER FOUNTAINS ARE REQUIRED THE PLAN IS ONLY
 SHOWING A SINGLE. PER FBC PL [B] 410.2
 MINIMUM NUMBER.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3. TEMPERED WATER REQUIRED AT THE LAVATORY IN
 BATHROOMS. PER FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 4. SHT. P2.0 THE DEVELOPED LENGTH OF THE VENT FOR P-3
 AND P-16 IN THE NORTH WEST CORNET OF ROOM 131 APPEARS
 TO BE OVER 40' IT SHALL BE SIZED ACCORDING TO FBC PL
 906.2
 VENTS EXCEEDING 40 FEET (12 192 MM) IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE.
  
 5. SHT. P3-0 THE NOTE ON THE PLAN FOR THE CONTINUATION
 OF THE BICARB AND RO SYSTEM IS ON ME-1 BUT THERE NOT IN
 THE PLAN SET PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 6. THE VENT FOR P-15 AND P-3 IN ROOM 139 CAN NOT RUN
 HORIZONTAL BELOW THE FLOOD LEVEL RIM OF THE FIXTURE IT
 CAN RUN AT A 45 ANGLE OR USE A AAV. PER FBC PL 905.4
 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.