| 2017-01-09 12:13:25 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. GRAB BARS TO BE MEASURE FROM FINISHED FLOOR TO TOP |
| | OF GRIPPING SURFACE. PER FBC PL 609.4 |
| | POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR |
| | CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM) |
| | MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE |
| | HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A |
| | BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1. |
| | |
| | 2.TWO WATER FOUNTAINS ARE REQUIRED THE PLAN IS ONLY |
| | SHOWING A SINGLE. PER FBC PL [B] 410.2 |
| | MINIMUM NUMBER. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | FBC ACC 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 3. TEMPERED WATER REQUIRED AT THE LAVATORY IN |
| | BATHROOMS. PER FBC PL 416.5 |
| | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 4. SHT. P2.0 THE DEVELOPED LENGTH OF THE VENT FOR P-3 |
| | AND P-16 IN THE NORTH WEST CORNET OF ROOM 131 APPEARS |
| | TO BE OVER 40' IT SHALL BE SIZED ACCORDING TO FBC PL |
| | 906.2 |
| | VENTS EXCEEDING 40 FEET (12 192 MM) IN DEVELOPED LENGTH |
| | SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE |
| | ENTIRE DEVELOPED LENGTH OF THE VENT PIPE. |
| | |
| | 5. SHT. P3-0 THE NOTE ON THE PLAN FOR THE CONTINUATION |
| | OF THE BICARB AND RO SYSTEM IS ON ME-1 BUT THERE NOT IN |
| | THE PLAN SET PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. THE VENT FOR P-15 AND P-3 IN ROOM 139 CAN NOT RUN |
| | HORIZONTAL BELOW THE FLOOD LEVEL RIM OF THE FIXTURE IT |
| | CAN RUN AT A 45 ANGLE OR USE A AAV. PER FBC PL 905.4 |
| | VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |