| 2016-12-08 09:52:37 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES |
| | PERMIT #16111217 |
| | 12/8/16 |
| | |
| | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR, AND SHOW THE AMOUNTS PER |
| | EACH AIR HANDLER. |
| | |
| | 2) PROVIDE AN EXHAUST FAN SCHEDULE ON THE PLAN. |
| | |
| | 3) MED WASTE ROOM FAN: A) PROVIDE A SIZING CALCULATION. |
| | B) INDICATE HOW MAKEUP AIR IS BEING PROVIDED. C) |
| | INDICATE THE SEQUENCE OF OPERATION FOR THE FAN. |
| | |
| | 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW AIR HANDLERS AND DUCTLESS SYSTEM- SECTION C403.2.1 |
| | FBC-14 ENERGY CONSERVATION. |
| | |
| | 5) SHEET M2.0: CHANGE THE SD LABEL TO FD IN THE MED |
| | RECORDS ROOM. |
| | |
| | 6) M3.0: PROVIDE MORE INFORMATION ABOUT THE USE OF THE |
| | VOLUME DAMPERS FOR TEMORARY SHUTDOWN OF THE SIR SUPPLY |
| | IN THE EXPANDED STATIONS ROOM. WHICH CODE, STANDARD, |
| | REGULATION, OR GUIDELINE ETC, IS REQUIRING THIS |
| | PROCEDURE? |
| | |
| | 7) PROVIDE A MECHANICAL ROOF PLAN INDICATING ALL |
| | REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR THE AIR |
| | INTAKES AS REQUIRED BY SECTION 401.4. |
| | |
| | 8) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| | PLANS FOR THE NEW AIR HANDLERS- SECTION 307. |
| | |
| | 9) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE NEW |
| | AC CONDNENSERS TO THE SLABS- SECTION 301.15. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |