| 2016-12-20 13:47:10 | 2000 CONTINENTAL DRIVE |
| | PERMIT #16111217 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | TITLE SHEET: PLANS INDICATE THIS OCCUPANCY TO BE A |
| | BUSINESS OCCUPANCY; HOWEVER, THIS APPEARS TO BE AN |
| | AMBULATORY HEALTHCARE OCCUPANCY PER NFPA 101 SECTION |
| | 3.3.188.1 AMBULATORY HEALTH CARE OCCUPANCY. AN |
| | OCCUPANCY USED TO PROVIDE SERVICES OR TREATMENT |
| | SIMULTANEOUSLY TO FOUR OR MORE PATIENTS THAT PROVIDES, |
| | ON AN OUTPATIENT BASIS, ONE OR MORE OF THE FOLLOWING: |
| | (1) TREATMENT FOR PATIENTS THAT RENDERS THE PATIENTS |
| | INCAPABLE OF TAKING ACTION FOR SELFPRESERVATION UNDER |
| | EMERGENCY CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS; |
| | (2) ANESTHESIA THAT RENDERS THE PATIENTS INCAPABLE OF |
| | TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY |
| | CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS; (3) |
| | EMERGENCY OR URGENT CARE FOR PATIENTS WHO, DUE TO THE |
| | NATURE OF THEIR INJURY OR ILLNESS, ARE INCAPABLE OF |
| | TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY |
| | CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS. |
| | |
| | TITLE SHEET: PLANS INDICATE THE APPLICABLE CODE AS |
| | "2000 NFPA 101 LIFE SAFETY CODE - CHAPTER 21." PLEASE |
| | JUSTIFY THE USE OF THIS CODE IN LIEU OF THE 5TH EDITION |
| | OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | CIVIL SHEET 1: PLAN INDICATES A NEW UNDERGROUND |
| | FIRELINE FOR A NEW FIRE SPRINKLER SYSTEM; HOWEVER, THE |
| | TITLE SHEET MAKES NO MENTION OF THE INTENT TO PROTECT |
| | THE BUILDING WITH AUTOMATIC SPRINKLERS. PER NFPA 24 |
| | SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE |
| | MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN |
| | BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | FIRE SPRINKLER DESIGN: ENGINEERED FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. PER SECTION 105.3.1.2(2) |
| | OF THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE |
| | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR |
| | ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER |
| | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | SHEET LS2.0: MEZZANINE SIZE APPEARS TO BE A SECOND |
| | FLOOR. PER NFPA 101 SECTION 8.6.10.2 AREA LIMITATIONS. |
| | THE AGGREGATE AREA OF MEZZANINES LOCATED WITHIN A ROOM |
| | SHALL NOT EXCEED ONE-THIRD THE OPEN AREA OF THE ROOM IN |
| | WHICH THE MEZZANINES ARE LOCATED. ENCLOSED SPACE SHALL |
| | NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE |
| | ROOM IN WHICH THE MEZZANINE IS LOCATED. |
| | |
| | NOTE: A SEPARATE PERMIT (UG FIRELINE) IS NEEDED FOR THE |
| | INSTALLATION OF A PRIVATE FIRE MAIN IN ACCORDANCE WITH |
| | NFPA 24. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |