  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] THE APPLICABLE NFPA 101 LIFE SAFETY CODE IN EFFECT
 IS THE 2012 EDITION. PLEASE CORRECT NOTE.
  
 2] SHOW THE WIRE-WAY SIZE IN ACCORDANCE WITH NEC 376 &
 378.
  
 3] PROVIDE FPL AVAILABLE FAULT CURRENT & SHOW AIC
 CALCULATIONS TO VERIFY SHORT-CIRCUIT RATING OF
 ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9.
  
 4] MARK EXTERIOR GFCI RECEPTACLE OUTLET AS WP/WR PER
 NEC 406.9(B).
  
 5] ADD A NOTE FOR ARC-FLASH WARNING LABEL ON ELECTRICAL
 EQUIPMENT PER NEC 110.16.
  
 6] PROVIDE EXIT/EMERGENCY COMBO IN NORTH EGRESS DOOR
 LEADING TO PUBLIC WAY PARKING. FBC 1006 & 1011.
  
 7] FIRE ALARM & LOW VOLTAGE SHALL BE UNDER A SEPARATE
 PERMIT. A NOTE SHALL SUFFICE.
  
 8] WHEN YOU RE-SUBMIT PLEASE FILL OUT " COMPLETION
 AGREEMENT & CONDITIONAL / PHASED OCCUPANCY REQUEST"
 FORM,
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  