| Plan Review Notes For Permit 16111205 |
| Permit Number |
16111205 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-08 03:14:47 | 1) NEW SHOWER VALVE SHALL BE OF THE PRESSURE -BALANCE, | | | THERMOSTATIC-MIXING OR COMBINATION | | | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPE WITH A | | | HIGH LIMIT STOPCOMPLYING WITH ASSE 1016 OR ASME | | | A112.18/CSA B125.1. 2014 FBCR SEC.P2708.3.INDICATE TYPE | | | OF SHOWER VALVE TO BE INSTALLED ON THE PLANS. | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE | | | WATERPROOFING SYSTEM FOR THE SHOWER. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 3) THE WATERPROOFING SYSTEM SHALL COMPLY WITH 2014 FBCR | | | SEC.P2709.2.4 AND ANSI A118.10. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|