| Notes |
| Date |
Text |
| 2016-12-08 03:33:42 | 1) INDICATE ON THE PLANS THE TYPE OF BASE/BACKER BOARD | | | THAT IS BEING INSTALLED FOR THE TILE IN THE SHOWER. | | | COMPLY WITH 2014 FBCR SECS.R702.3.8, R702.3.8.1 & | | | R702.4.1. | | | 2) SHOWER GLASS DOORS SHALL COMPLY WITH 2014 FBCR | | | SEC.R308.1. SUBMIT MANUF.SPECIFICATIONS FOR THE GLASS | | | DOORS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUPPLY MORE INFORMATION FOR THE CEILING REPAIR IN | | | THE GARAGE. WHAT EXACTLY IS BEING DONE? "REPAIR | | | CEILING" IS TOO VAGUE. IS DRYWALL BEING REMOVED AND | | | REPLACED" IF SO HOW MUCH AND WHERE IS IT BEING | | | REPLACED? CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|