| Plan Review Notes For Permit 16111164 |
| Permit Number |
16111164 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-05 18:43:04 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- CONDENSER UNIT MANUFACTURER WAS CHANGED FOR A | | | COMFORTMAKER UNIT. THE AIR HANDLER UNIT SHOWN ON THE | | | EQUIPMENT SCHEDULE IS A GOODMAN UNIT. CLARIFY WHY | | | SPECIFYING TWO DIFFERENT MANUFACTURER'S. PROVIDE THE | | | AHRI CERTIFICATE FOR THE EQUIPMENT LISTED IN THE | | | REVISED EQUIPMENT SCHEDULE. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|