| 2016-12-30 09:34:11 | FAILED |
| | |
| | 1) THE PLANS SHOW THE RELOCATION OF THE ABOVE GROUND |
| | TANK FROM A LOCATION HIDDEN FROM PUBLIC BEHIND THE |
| | BUILDING TO A PUBLICALLY VISIBLE AREA ON THE SIDE OF |
| | THE SITE. PLEASE EXPLAIN THIS PROPOSED CHANGE. ZONING |
| | STAFF DOES NOT CURRENTLY SUPPORT THIS RELOCATION. IF |
| | THE RELOCATION IS APPROVED BY ZONING STAFF, THEN: |
| | |
| | A. SHEET ASP DOES NOT SHOW SCREENING FOR THE RELOCATED |
| | ABOVE GROUND TANK OR THE PUMP. |
| | B. THE LOADING ZONE HAS NOW BEEN MOVED INTO THE EXIT |
| | DRIVE AREA. PROVIDE DIMENSIONS ON THE PLAN TO VERIFY |
| | THAT THERE IS SUFFICIENT DRIVEWAY WIDTH FOR A CAR TO |
| | EXIT THE SITE WHILE A VEHICLE IS PARKED IN THE LOADING |
| | ZONE. |
| | |
| | 2) THERE ARE DISCREPANCIES BETWEEN SHEET ASP AND THE |
| | CIVIL SHEETS. ALL PLANS SHALL SHOW THE SAME CONDITIONS. |
| | EXAMPLES: |
| | |
| | A. SOME OF THE LIGHT POLES ARE NOT SHOWN IN THE SAME |
| | LOCATION ON BOTH SETS OF PLANS (CONFLICT WITH |
| | ELECTRICAL SITE PLAN AS WELL). |
| | B. THE CIVIL PLANS SHOW A PROPOSED WATER METER AND A |
| | BACKFLOW PREVENTER ON THE SOUTHEAST CORNER OF THE SITE, |
| | WHICH ARE NOT SHOWN ON THE ARCHITECTURAL SITE PLAN. |
| | C. THE FIRE HYDRANT IS NOT SHOWN ON SHEET ASP. |
| | |
| | 3) THE REVISED PLANS SHOW THAT THE PARKING SPACES HAVE |
| | ADDED CURBS AND ARE STRIPPED AT 18 FEET IN DEPTH. THE |
| | APPROVED PLANS SHOWED 16 FEET IN DEPTH WITH A TWO FOOT |
| | OVERHANG AT THE CURB. WHERE DID THE EXTRA TWO FEET COME |
| | FROM? THE BUILDING SETBACK AND THE DRIVE AISLE SEEM TO |
| | BE THE SAME AS THE PERMIT AND SITE PLAN APPROVED PLANS. |
| | ADDITIONALLY, THE CROSS SECTIONS SHOW THE NORTH |
| | PROPERTY LINE LANDSCAPE AREA FOUR FEET LESS IN WIDTH |
| | THAN THE APPROVED PERMIT CROSS-SECTION. NO EXPLANATION |
| | IS GIVEN FOR THESE CHANGES. |
| | |
| | 4) PLEASE EXPLAIN HOW THE LANDSCAPE BUFFER WILL BE |
| | INSTALLED WITH THE NEW 3:1 SLOPE BERM AND DITCH ALONG |
| | THE NORTH PROPERTY LINE. |
| | |
| | 5) DUE TO THE CHANGES TO THE PLANS, PRIOR TO THE |
| | ISSUANCE OF A CO OF THE BUILDING, AS BUILT SITE, CIVIL |
| | AND LANDSCAPE PLANS SHALL BE SUBMITTED TO THE PLANNING |
| | DIVISION AS PART OF A MINOR SITE PLAN AMENDMENT. |
| | |
| | 6) THE FOLLOWING ADDITIONAL SEPARATE PERMITS, WITH |
| | PLANS, ARE REQUIRED: |
| | |
| | A. CONSTRUCTION FENCE - PLEASE NOTE SCREENING IS |
| | REQUIRED. |
| | B. PARKING LOT STRIPING |
| | C. IRRIGATION |
| | D. BICYCLE RACK |
| | E. PERMANENT FENCE AND GATES |
| | F. LANDSCAPE. THE TRANSFORMER SHALL BE SHOWN ON THE |
| | LANDSCAPE PLANS. |
| | G. SITE LIGHTING. PHOTOMETRICS SHALL BE INCLUDED. |
| | |
| | 7) PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY, ALL |
| | GROUND MOUNTED UTILITY EQUIPMENT SHALL BE SCREENED FROM |
| | PUBLIC VIEW. THE PLANS SHALL SHOW HOW THIS OCCURS. |
| | |