| 2016-12-19 17:11:58 | JOB PERMIT NUMBER: 16111142 |
| | JOB ADDRESS: 428 30TH ST |
| | WEST PALM BEACH FLORIDA |
| | DATE: DECEMBER 19, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] CORRECT EXISTING PANEL SCHEDULE CIRCUIT #24, #26 FOR |
| | THE CLOTHES DRYER TO A 10 AWG WITH A 30 AMP BKR |
| | (TYPICAL). FBC-107.3.5.3 |
| | |
| | 2] ADD GENERAL ELECTRICAL NOTES FOR AFCI PROTECTION & |
| | TAMPER RESISTANT RECEPTACLES. FBC-R SECTIONS E3902.13 & |
| | E4002.14 |
| | |
| | 3] RECESSED LIGHTING IN THE BUILDING THERMAL ENVELOPE |
| | SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UN-CONDITIONED SPACES (IF INSTALLED IN |
| | THERMAL INSULATION THE HOUSING SHALL BE LISTED |
| | IC-RATED). FBC-E SECTION R402.4.4 A NOTE WILL SUFFICE. |
| | |
| | 4] PERMANENT INSTALLED LUMINAIRES SHALL BE 75 % HIGH |
| | EFFICIENT. FBC-E SECTION R404.1 A NOTE WILL SUFFICE. |
| | |
| | 5] ELEVATOR SHORT CIRCUIT & GROUND FAULT OVERCURRENT |
| | PROTECTION SHALL BE SIZED IN ACCORDANCE WITH NEC |
| | 620.61. |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |