| 2016-12-20 12:43:49 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ***NOTE: |
| | ADDRESS WAS CHANGED FROM 428 30TH ST. TO 432 30TH ST. |
| | BECAUSE THERE ARE 5 BUILDINGS IN THIS LOT AND THIS IS |
| | THE BUILDING WHERE WORK IS PERFORMED. JG. |
| | |
| | |
| | 1- PLANS SUBMITTED SHOW AN "EXISTING AVIARY". PLANS |
| | SHOW A LARGE STRUCTURE. ACCORDING TO CITY RECORDS THERE |
| | ARE NO PERMITS FOR THIS STRUCTURE. PROVIDE COMPLETE |
| | PLANS, ELEVATIONS, DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION AND INSTALLATION OF THIS STRUCTURE AS |
| | REQUIRED BY SEC. R301.2.1.1.1 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | NOTE: COORDINATE WITH ZONING PROPOSED USE OF THE |
| | STRUCTURE. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ELEVATOR ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | B) LANAI ENTRY DOOR TO BE REPLACED AS SHOWN ON PLANS. |
| | |
| | C) ELEVATOR STOREFRONT SYSTEM AS SHOWN ON PLANS. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| | NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | RE-FRAMING AND REINFORCEMENT AT THE CORNER AREA WHERE |
| | NEW ELEVATOR SHAFT IS GOING TO BE BUILT. NOTE: THIS |
| | APPLIES TO FIRST FLOOR, SECOND FLOOR AND ROOF AREA. |
| | SPECIFY ALL FRAMING MEMBER AND CONNECTORS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- PROVIDE COMPLETE FRAMING DETAILS DETAILS AND |
| | SPECIFICATIONS FOR THE FRAMING OF THE ELEVATOR |
| | HOISTWAY. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR THE FRAMING OF THE NEW STOREFRONT WINDOWS SHOWN ON |
| | PLANS. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |
| | 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR THE FRAMING OF THE NEW ENTRY DOOR SHOWN ON PLANS. |
| | SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 8- STRUCTURAL NOTES ON SHEET S-1: |
| | A) REVISE THE WIND LOAD REFERENCE. THE CURRENT ASCE-7 |
| | IS THE 2010 EDITION NOT 2014. REVISE AS REQUIRED. |
| | CHAPTER 553 F.S. |
| | |
| | B) CLEARLY SPECIFY THE WIND LOAD. WHAT IS THE 140 MPH |
| | WIND LOAD?. SPECIFY THE ULTIMATE WIND LOAD AND THE |
| | NOMINAL WIND LOAD. SEC. R301.2.1.3 FBC-RESIDENTIAL. . |
| | NOTE: THE CITY ULTIMATE WIND SPEED IS 170 MPH. |
| | |
| | C) UPDATE ALL THE CODES REFERENCED. SEE CHAPTER 46 OF |
| | FBBC-RESIDENTIAL FOR THE CURRENT EDITION OF THE |
| | REFERENCED STANDARDS AND REVISE AS REQUIRED. |
| | |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |