| 2016-12-29 07:02:30 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16111129 | | | 12/28/16 | | | | | | 1) THE 3.5.02 PLAN SHEET HAS DETAILS AND PRINT THAT IS | | | ILLEGFIBLE. PLEASE PROVIDE AN ENLARGED SHEET. | | | | | | 2) REFER TO TABLE 1509.6.5 FBC-14 BUILDING AND PROVIDE | | | A DRAWING THAT INDICATES THE CLEARANCE DISTANCE | | | MEASUREMENTS FROM THE ROOF SURFACE TO THE UNDERSIDE OF | | | THE DOC UNITS. | | | | | | 3) SHOW THE PIPING LAYOUT AND INDICATE HOW THE PIPING | | | WILL MBE SUPPORTED ON THE ROOF. | | | | | | 4) INDICATE COMPLIANCE WITH SECTION 501.3.1 (2) FOR | | | EXHAUST OUTLET CLEARSANCES TO AIR INTAKES | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|