| Plan Review Notes For Permit 16111051 |
| Permit Number |
16111051 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-10 08:57:46 | 1) INDICATE THE DELIVERY PRESSURE AND THE PRESSURE DROP | | | ON THIS SYSTEM. THE SIZING DOCUMENTS SUBMITTED FOR THE | | | TRACPIPE SHOW THAT A 3/4" LINE IS UNDERSIZED TO SUPPLY | | | THE BTU LOAD FOR BOTH TANKLESS WATER HEATERS AT 1/2 LB. | | | SUPPLY PRESSURE WITH A PRESSURE DROP OF 0.5" W.C.FOR | | | BOTH AN 80 FEET AND 10 FEET RUN. | | | 2) IF THIS IS A 2 LB. SYSTEM, SHOW THE LOCATION OF THE | | | PRESSURE REGULATORS ON THE PLAN. PLEASE SUBMIT AN | | | ISOMETRIC DRAWING THAT CLEARLY REFLECTS THE ENTIRE GAS | | | SYSTEM, PIPE SIZES, TOTAL LENGTH FROM THE POINT OF | | | DELIVERY TO THE FURTHEST OUTLET, ETC. | | | SEE THE PREVIOUS GAS REVIEW COMMENTS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|