Plan Review Notes
Plan Review Notes For Permit 16111045
Permit Number 16111045
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-01 09:16:5612/02/16 ENGINEER INSPECTION LETTER WAS DELIVERED TO
 ART LANGE (INSPECTOR) FOR INSPECTIONS RESULTS. JG
  
  
  
  
 RESIDENTIAL (R2) REVISION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- INFORMATION ON THE PLANS SUBMITTED IS EXTREMELY
 LIGHT IN SOME AREAS AND IS BARELY LEGIBLE. NEED TO
 PROVIDE LEGIBLE PLANS THAT ARE SUITABLE FOR READING AND
 ARE ADEQUATE FOR THE RECORDS RETENTION PROGRAM. REVISE
 AS REQUIRED. SEC.107.2.1.4 CITY AMENDMENTS.
  
 2- PLANS SUBMITTED SHOW CLOUDED AREAS THAT ARE DELETING
 INFORMATION THAT WAS ALREADY APPROVED AND IT'S SHOWN ON
 THE CITY RECORDS. THAT INFORMATION CAN NOT BE DELETED
 BECAUSE IT WAS PART OF THE SCOPE OF WORK. WORK WAS DONE
 FOR THOSE ITEMS THAT WERE DELETED. NEED TO
 RE-INCORPORATE SUCH INFORMATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- NEED TO COMPLY WITH PROVISO DATED 01/25/16. BUILDING
 REVIEW WAS APPROVED WITH THE CONDITION THAT INFORMATION
 WAS GOING TO BE REVISED. SEE BELOW FOR COPY OF PROVISO
 THAT WAS PASTED ON THE APPROVED PLANS:
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE SIZE OF HEATING/COOLING UNIT FOR NEW BEDROOM:
 SIZE OF HEATING AND COOLING WALL UNIT SHOWN ON PLANS IS
 OVERSIZED FOR THE NEW BEDROOM. 8,000 BTU UNIT IS
 OVERSIZED FOR A ROOM WITH LESS THAN 100S.F . PROVIDE
 EQUIPMENT SIZING CALCULATIONS. SEC. C403.2.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). EQUIPMENT
 CAN NOT EXCEED THE CALCULATED LOADS. SEC. C403.2.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]