| 2016-12-05 07:09:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16111042 | | | 12/5/16 | | | | | | 1) THE HP BTUH CAPACITIES AND EFFICIENCY RATINGS SHOWN | | | ON THE EQUIPMENT SCHEDULE DON'T MATCH THE CAPACITIES | | | SHOWN IN THE ENERGY CALCULATIONS. | | | | | | 2) INDICATE THE REQUIRED CLEARANCE DISTANCES FOR THE | | | O/A INTAKES- SECTION 401.4. | | | | | | 3) INDICATE HOW THE O/A INTAKE OPENINGS WILL BE | | | PROTECTED- SECTION 401.5. | | | | | | 4) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION AND PROVIDE SHUTOFF DAMPER CONTROLS FOR | | | THE O/A INTAKES. PLEASE NOTE IF MOTORIZED DAMPERS ARE | | | TO BE INSTALLED, THEY SHALL BE IN COMPLIANCE WITH | | | SECTION C402.4.5.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|