Plan Review Notes
Plan Review Notes For Permit 16111042
Permit Number 16111042
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-01 14:08:56PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SPECIFY ON THE PLANS THE REQUIRED WIRING METHODS
 SUITABLE FOR A HEALTH CARE FACILITY/ EXAM ROOMS AS
 DEFINED IN ARTICLE 517 OF THE NATIONAL ELECTRICAL CODE.
 NEC 517.1, 517.11, 517.13
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
 [email protected]
  