Plan Review Notes
Plan Review Notes For Permit 16111038
Permit Number 16111038
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-14 09:07:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS
 WITH ELECTRICAL REQUIREMENTS FOR THE ELECTRIC HEAT PUMP
 POOL HEATER. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS THAT
 SHOW THE EXISTING ELECTRICAL IS ADEQUATE FOR THE NEW
 POOL EQUIPMENT. THE NAME, LICENSE NUMBER AND SIGNATURE
 OF THE PERSON PROVIDING THE CALCULATIONS ARE REQUIRED
 TO BE ON THEM. FBCR-E3602.2
  
 3) AN ELECTRICAL SUB-PERMIT IS REQUIRED. FBC 105.1
  