2016-12-05 13:55:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111013
 12/5/16
  
 1) CORRECT THE NOTE INDICATING ALL ABOVEGROUND PIPE
 2-1/2- 8" IS EXISTING. THE PLAN SHOWS NEW PIPING TO BE
 INSTALLED.
  
 2) INDICATE HOW THE NEW 2-1/2 AND 1" SPRINKLER PIPING
 WILL BE SUPPORTED AT THE BUILDING AND AT THE DUST
 COLLECTOR. THE CUT AND PASTE DETAIL OF THE BAR JOIST
 HANGER IS NOT APPLICABLE.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 WPB AMENDMENTS TO THE FBC. (SEE ALSO SECTION 107.3.5).
  