Plan Review Notes
Plan Review Notes For Permit 16111013
Permit Number 16111013
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-11-23 17:24:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROVIDE AN ISOLATION VALVE TO DUST COLLECTOR SYSTEM
 AND TEST AT 200PSI.
  
 THE PROPOSED PROJECT IS ADDING ALL NEW PIPING AND
 HEADS, IT DOES NOT INVOLVE RELOCATED HEADS AND, IT CAN
 BE ISOLATED.
  
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 ADDITIONALLY, THIS IS A HIGHER THAN NORMAL HAZARD
 PROTECTION SYSTEM WHERE SYSTEM INTEGRITY IS ESSENTIAL.
  
  
 2) ADDITIONALLY, AN ISOLATION VALVE WILL ALSO FUNCTION
 IN THE CASE OF COLLECTOR SPRINKLER ACTIVATION AND SHUT
 DOWN WHILE MAINTAINING PORTECTION THROUGHOUT THE
 BUILDING.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  