| Plan Review Notes For Permit 16111009 |
| Permit Number |
16111009 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-24 09:10:53 | ****CORRECTIONS**** | | | REVISED 1/27/17 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE CALCULATIONS SHOW A DP OF +30.2 / -83.6. SEE | | | SHEET S102, THIS DOES NOT MEET THE MINIMUM DESIGN | | | PRESSURES SPECIFIED BY THE ENGINEER OF RECORD. | | | | | | 2. THE COMMENTS WERE ADDRESSED BY THE CONTRACTOR RATHER | | | THAN THE ENGINEER. AS THE CONTRACTOR IS NOT A DESIGN | | | PROFESSIONAL AND NOT LICENSED TO DESIGN THE SKYLIGHT, | | | THE BUILDING OFFICIAL HAS DETERMINED THAT IT IS | | | ACCEPTABLE FOR THE ARCHITECT OR ENGINEER OF RECORD TO | | | REVIEW THE LETTER PREPARED BY THE CONTRACTOR AND | | | CERTIFY THE INFORMATION ON THE LETTER ALONG WITH THE | | | RELATED DOCUMENTS. OR, SKYLIGHT ENGINEER CAN REVISE | | | DOCUMENTS TO INCORPORATE THE INFORMATION. | | | | | | 3. THE ARCHITECT'S REVIEW STAMP STATES THAT THIS WAS | | | REVIEWED FOR "GENERAL CONFORMANCE." DOES THIS INCLUDE | | | REVIEWING REQUIREMENTS SUCH AS SUPERIMPOSED LOADS ON | | | THE STRUCTURE, DESIGN PRESSURES? EITHER ARCHITECT OR | | | ENGINEER SHOULD REVIEW THESE ITEMS. IF THIS IS NOT | | | WITHIN THE PURVIEW OF THE ARCHITECT'S RESPONSIBILITY, | | | PLEASE HAVE THE SUBMITTAL REVIEWED BY THE ENGINEER. | | | | | | | | | | | | |
|