Plan Review Notes
Plan Review Notes For Permit 16111009
Permit Number 16111009
Review Stop B
Sequence Number 2
Notes
Date Text
2017-01-24 09:10:53****CORRECTIONS****
 REVISED 1/27/17
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE CALCULATIONS SHOW A DP OF +30.2 / -83.6. SEE
 SHEET S102, THIS DOES NOT MEET THE MINIMUM DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD.
  
 2. THE COMMENTS WERE ADDRESSED BY THE CONTRACTOR RATHER
 THAN THE ENGINEER. AS THE CONTRACTOR IS NOT A DESIGN
 PROFESSIONAL AND NOT LICENSED TO DESIGN THE SKYLIGHT,
 THE BUILDING OFFICIAL HAS DETERMINED THAT IT IS
 ACCEPTABLE FOR THE ARCHITECT OR ENGINEER OF RECORD TO
 REVIEW THE LETTER PREPARED BY THE CONTRACTOR AND
 CERTIFY THE INFORMATION ON THE LETTER ALONG WITH THE
 RELATED DOCUMENTS. OR, SKYLIGHT ENGINEER CAN REVISE
 DOCUMENTS TO INCORPORATE THE INFORMATION.
  
 3. THE ARCHITECT'S REVIEW STAMP STATES THAT THIS WAS
 REVIEWED FOR "GENERAL CONFORMANCE." DOES THIS INCLUDE
 REVIEWING REQUIREMENTS SUCH AS SUPERIMPOSED LOADS ON
 THE STRUCTURE, DESIGN PRESSURES? EITHER ARCHITECT OR
 ENGINEER SHOULD REVIEW THESE ITEMS. IF THIS IS NOT
 WITHIN THE PURVIEW OF THE ARCHITECT'S RESPONSIBILITY,
 PLEASE HAVE THE SUBMITTAL REVIEWED BY THE ENGINEER.
  
  
  
  