| 2016-12-01 18:03:57 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. SKYLIGHT CALCS COVER SHEET INCLUDES A STATEMENT |
| | ?GLAZING DESIGNED BY OTHERS.? IT IS NOT CLEAR WHAT THIS |
| | REFERS TO, FBC 107. |
| | |
| | 2. THE GLASS PROPOSED IS NOT CLEAR. THE GLASS LOAD |
| | RESISTANCE REPORT STATES THAT OUTBOARD LITE IS ? FULY |
| | TEMPERED, INBOARD LITE IS ? IN HEAT STRENGTHENED, IT IS |
| | NOT CLEAR HOW THIS CORRELATES WITH THE SERIES 500 RIDGE |
| | SKYLIGHT SPECIFICATIONS 3 B, WHICH APPEARS TO INDICATE |
| | ADDITIONAL LAYERS OF GLASS. |
| | |
| | 3. THE GLASS SPEC REFERENCES SB72, PROVIDE SPECS AND |
| | TEST REPORT OR PRODUCT APPROVAL, FBC 107. |
| | |
| | 4. THE SPECIFICATIONS STATE THAT THIS IS A SMALL |
| | MISSILE HURRICANE TESTED PRODUCT. REVISE TO CLARIFY, IS |
| | THE PRODUCT TESTED AS STATED? IF IT HAS BEEN TESTED, |
| | PROVIDE A COPY OF THE TEST. IF THE PRODUCT UTILIZES A |
| | TESTED PRODUCT, PLEASE REVISE PLAN TO CLARIFY. |
| | |
| | 5. SHEET 1 OF 6 DESIGN REQUIREMENTS STATES THAT THE |
| | CURB AS SUPPLIED BY OTHERS SHOULD ACCEPT ALL LOADING |
| | WITHOUT DEFLECTION. WHO HAS REVIEWED THIS? THE |
| | ARCHITECT?S REVIEW STAMP IS NOT CLEAR THAT THIS THE |
| | CURB WILL ACCEPT LOADING. EITHER HAVE THE ARCHITECT |
| | CLARIFY OR HAVE THE ENGINEER (WHO DESIGNED THE CURB) |
| | REVIEW. |
| | |
| | 6. FBC TABLE 601, 1 HOUR FIRE RATING REQUIRED FOR THE |
| | ROOF (BUILDING TYPE IIA). |
| | |
| | |
| | |