2016-12-01 18:03:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SKYLIGHT CALCS COVER SHEET INCLUDES A STATEMENT
 ?GLAZING DESIGNED BY OTHERS.? IT IS NOT CLEAR WHAT THIS
 REFERS TO, FBC 107.
  
 2. THE GLASS PROPOSED IS NOT CLEAR. THE GLASS LOAD
 RESISTANCE REPORT STATES THAT OUTBOARD LITE IS ? FULY
 TEMPERED, INBOARD LITE IS ? IN HEAT STRENGTHENED, IT IS
 NOT CLEAR HOW THIS CORRELATES WITH THE SERIES 500 RIDGE
 SKYLIGHT SPECIFICATIONS 3 B, WHICH APPEARS TO INDICATE
 ADDITIONAL LAYERS OF GLASS.
  
 3. THE GLASS SPEC REFERENCES SB72, PROVIDE SPECS AND
 TEST REPORT OR PRODUCT APPROVAL, FBC 107.
  
 4. THE SPECIFICATIONS STATE THAT THIS IS A SMALL
 MISSILE HURRICANE TESTED PRODUCT. REVISE TO CLARIFY, IS
 THE PRODUCT TESTED AS STATED? IF IT HAS BEEN TESTED,
 PROVIDE A COPY OF THE TEST. IF THE PRODUCT UTILIZES A
 TESTED PRODUCT, PLEASE REVISE PLAN TO CLARIFY.
  
 5. SHEET 1 OF 6 DESIGN REQUIREMENTS STATES THAT THE
 CURB AS SUPPLIED BY OTHERS SHOULD ACCEPT ALL LOADING
 WITHOUT DEFLECTION. WHO HAS REVIEWED THIS? THE
 ARCHITECT?S REVIEW STAMP IS NOT CLEAR THAT THIS THE
 CURB WILL ACCEPT LOADING. EITHER HAVE THE ARCHITECT
 CLARIFY OR HAVE THE ENGINEER (WHO DESIGNED THE CURB)
 REVIEW.
  
 6. FBC TABLE 601, 1 HOUR FIRE RATING REQUIRED FOR THE
 ROOF (BUILDING TYPE IIA).
  
  
  