Plan Review Notes
Plan Review Notes For Permit 16111006
Permit Number 16111006
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-11-23 16:39:3912/19/16
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE APPLICANT PROVIDED ADDITIONAL INFORMATION VIA
 EMAIL REGARDING THE COMMENTS BELOW AND THEY WERE ADDED
 TO THE PACKET.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PALN INDICATES A REVISION TO A
 1,000GAL TANK. THERE IS A CLOUD REVISION NOTE
 INDICATING "TANK WILL BE 4' FROM PROPERTY LINE". A SPEC
 SHEET CONTAINED IN THE PACKET INDICATES THAT TANKS 501
 - 2000GAL, 10FT FROM PROPERTY LINE AND 10FT FROM THE
 BUILDING.
  
 ADDITIONALLY, PER NFPA 58, LIQUEFIED PETROLEUM GAS CODE
 , CHAPTER 6 INSTALLATION OF LP-GAS SYSTEMSTABLE 6.3.1.
 THE TANK SHALL BE SEPARATED BY10FT.
  
 THE TANK SHALL BE INSTALLED 10FT FROM THE NEAREST
 BUILDING AND PROPERTY LINE.
  
 THE TANK APPEARS TOO LARGE FOR THE SITE AND OR ACCURATE
 DIMENSIONS ARE NOT PROVIDED.
  
 PLEASE PROVIDE ACCURATE/VERIFIABLE SITE DIMENSIONS THAT
 MEET SPECS AND CODE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  