2017-02-02 11:36:00RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED.
 ACCORDING TO PLANS (SHEET 01) THE EXISTING LIVING AREA
 IS 1945 S.F. AND THE LIVING ROOM EXTENSION IS 351 S.F.
 THEREFORE, THE TOTAL AREA IS 2296 S.F. NOT 1967 S.F..
 REVISE AS REQUIRED. SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 2- THERE IS NOT INFORMATION IF THE EXISTING A/C UNIT IS
 ADEQUATE TO TAKE THE ADDITIONAL LOAD OR IF NEW A/C WILL
 BE REQUIRED. IF EQUIPMENT NEEDS TO BE REPLACED, THEN
 PROVIDE COMPLETE EQUIPMENT INFORMATION ON THE EQUIPMENT
 SIZING CALCULATIONS AND PLANS. SEC. 107.3.5.3(10). CITY
 AMENDMENTS AND SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  