| Plan Review Notes For Permit 16110992 |
| Permit Number |
16110992 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-02 11:36:00 | RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED. | | | ACCORDING TO PLANS (SHEET 01) THE EXISTING LIVING AREA | | | IS 1945 S.F. AND THE LIVING ROOM EXTENSION IS 351 S.F. | | | THEREFORE, THE TOTAL AREA IS 2296 S.F. NOT 1967 S.F.. | | | REVISE AS REQUIRED. SEC. R403.6.1 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | 2- THERE IS NOT INFORMATION IF THE EXISTING A/C UNIT IS | | | ADEQUATE TO TAKE THE ADDITIONAL LOAD OR IF NEW A/C WILL | | | BE REQUIRED. IF EQUIPMENT NEEDS TO BE REPLACED, THEN | | | PROVIDE COMPLETE EQUIPMENT INFORMATION ON THE EQUIPMENT | | | SIZING CALCULATIONS AND PLANS. SEC. 107.3.5.3(10). CITY | | | AMENDMENTS AND SEC. R403.6.1 FBC-ENERGY CONSERVATION, | | | 5TH EDITION (2014). | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS.. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|