2017-02-01 18:49:38RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
  
 NOTE:
 OLD SETS WERE VOIDED. SHEETS 03 AND E-1 WERE REVISED
 BUT THEY WERE NOT REPLACED BY THE OLD ONES. ONE OF THE
 VOIDED SETS DON'T HAVE THE ARCHITECT'S SEAL AND
 SIGNATURE. PLEASE PROVIDE TWO COMPLETE SETS SIGNED AND
 SEALED FOR PROPER PROCESSING.
  
  
  
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT NEED TO CERTIFY AT
 THE BOTTOM OF THE FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). NOTE:
 PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S
 CERTIFICATION.
  
 B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 THE CALCULATIONS ARE DONE FOR THE ENTIRE HOUSE., THIS
 IS AN EXISTING CONSTRUCTION PLUS THE ADDITION. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) ITEM # 6 IS INCORRECT. ACCORDING TO PLANS (SHEET 01)
 THE EXISTING LIVING AREA IS 1945 S.F. AND THE LIVING
 ROOM EXTENSION IS 351 S.F. THEREFORE, THE TOTAL AREA IS
 2296 S.F. NOT 1967 S.F.. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) ITEM #8 IS INCORRECT. ACCORDING TO PLANS THERE IS NO
 CRAWLSPACE. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE THE NAME (NOT JUST THE SIGNATURE) OF THE
 PERSON WHO PREPARED THE ENERGY CALCULATIONS AS REQUIRED
 BY SEC. R405.4.2 FBC-ENERGY CONSERVATION.
  
 F) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 IS INCORRECT.
 THERE ARE NOT SHINGLES ON THIS HOUSE. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED, WHEN ENERGY CALCULATIONS ARE NOT USING THE
 DEFAULT FACTOR FOR GLAZING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SLIDING GLASS WINDOWS AS SHOWN ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) WINDOWS AS SHOWN ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) SIMPSON STRUCTURAL CONNECTOR H10S AS SPECIFIED ON
 PLANS. NOTE: FLORIDA PRODUCT APPROVAL "F25" SPECIFIED
 ON SHEET 03 IS NOT A VALID FLORIDA PRODUCT APPROVAL
 NUMBER. REVISE AS REQUIRED. ALSO, FLORIDA PRODUCT
 APPROVALS LISTED ON SHEET D-1 ARE NO CURRENT. UPDATE TO
 THE CURRENT 2014 CODE.
 NOTE: JAX APEX TECHNOLOGY COVER PAGE OF REPORT NO
 SIM201501 SUBMITTED IS NOT AN OFFICIAL PRODUCT APPROVAL
 AND IT DOESN'T LIST SPECIFIED CONNECTORS. PROVIDE
 FLORIDA PRODUCT APPROVAL (OR MIAMI-DADE) COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGNER OF
 RECORD TO LIST EACH FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO EACH SPECIFIED CONNECTOR.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 5- TRUSS PACKAGE SUBMITTED:
 A) ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT COPY) AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SUBMITTED SAME
 SHEETS AGAIN.
  
 B) COVER PAGE IS MISSING THE INFORMATION OF THE DESIGN
 PROFESSIONAL OF RECORD. FAC SEC. 61G15-31.003.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SUBMITTED SAME
 SHEETS AGAIN.
  
 C) NEED THE TITLE BLOCK OF THE TRUSS ENGINEER ON EACH
 DRAWING AS REQUIRED BY FAC SEC. 61G15-31.003.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SUBMITTED SAME
 SHEETS AGAIN.
  
 D) DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE
 ALL TRUSS DRAWINGS AS REQUIRED BY FAC SEC.
 61G15-31.003.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SUBMITTED SAME
 SHEETS AGAIN.
  
 6- NEW COMMENT: CLARIFY WHAT IS THE PURPOSE OF
 SUBMITTING LETTER FOR "EQUIVALENCE OF PUBLISHED
 VERSIONS OF ASTM D1761 AND ASTM D7147."?
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  