| Plan Review Notes For Permit 16110992 |
| Permit Number |
16110992 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-20 10:06:42 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS TO | | | VERIFY THAT EXISTING A/C UNIT IS ADEQUATE FOR THE | | | ADDITIONAL LOAD. SEC. R403.6.1 FBC-ENERGY CONSERVATION, | | | 5TH EDITION (2014). | | | NOTE: IF EQUIPMENT NEEDS TO BE REPLACED, THEN PROVIDE | | | COMPLETE EQUIPMENT INFORMATION ON THE EQUIPMENT SIZING | | | CALCULATIONS AND PLANS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS.. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|