2016-12-20 10:06:42RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS TO
 VERIFY THAT EXISTING A/C UNIT IS ADEQUATE FOR THE
 ADDITIONAL LOAD. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: IF EQUIPMENT NEEDS TO BE REPLACED, THEN PROVIDE
 COMPLETE EQUIPMENT INFORMATION ON THE EQUIPMENT SIZING
 CALCULATIONS AND PLANS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  