Plan Review Notes
Plan Review Notes For Permit 16110986
Permit Number 16110986
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-22 17:02:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110986
 11/21/16
  
 1) THE SUBMITTED ARCHITECTURAL PLAN MUST BEAR THE
 SIGNATURE AND SEAL OF THE ARCHITECT PER SECTION
 61G1-16.003 FLORIDA ADMINISTRATIVE CODE. WHY IS THIS
 PLAN BEING SUBMITTED WHEN NEITHER THE WALK-IN COOLER OR
 ICE MAKER ARE NUMBERED AND INCLUDED IN THE EQUIPMENT
 SCHEDULE? PLEASE NOTE THAT THE LOCATION OF THE WALK IN
 COOLER DOOR AS SHOWN IN THE SUBMITTAL DOESN'T MATCH THE
  
 LOCATION ON THE PLAN.
  
 2) THE ALUMINUM ROOF STAND SUBMITTAL HAS A COPIED
 ENGINEER'S SEAL. REFER TO SECTION 61-G15-23.002 AND
 PROVIDE A CLEAR, LEGIBLE SUBMITTAL WITH AN ORIGINAL
 SIGNATURE AND SEAL BY THE ENGINEER OF RECORD.
  
 3) PROVIDE A DRAWING INDICATING THE LOCATION OF THE
 CONDENSER ON THE ROOF WITH REQUIRED CLEARANCE DUISTANCE
 JMEASUREMENTS TO THE ROOF EDGES- SEE SECTION 304.11
 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  