| Plan Review Notes For Permit 16110986 |
| Permit Number |
16110986 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-22 17:02:24 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110986 | | | 11/21/16 | | | | | | 1) THE SUBMITTED ARCHITECTURAL PLAN MUST BEAR THE | | | SIGNATURE AND SEAL OF THE ARCHITECT PER SECTION | | | 61G1-16.003 FLORIDA ADMINISTRATIVE CODE. WHY IS THIS | | | PLAN BEING SUBMITTED WHEN NEITHER THE WALK-IN COOLER OR | | | ICE MAKER ARE NUMBERED AND INCLUDED IN THE EQUIPMENT | | | SCHEDULE? PLEASE NOTE THAT THE LOCATION OF THE WALK IN | | | COOLER DOOR AS SHOWN IN THE SUBMITTAL DOESN'T MATCH THE | | | | | | LOCATION ON THE PLAN. | | | | | | 2) THE ALUMINUM ROOF STAND SUBMITTAL HAS A COPIED | | | ENGINEER'S SEAL. REFER TO SECTION 61-G15-23.002 AND | | | PROVIDE A CLEAR, LEGIBLE SUBMITTAL WITH AN ORIGINAL | | | SIGNATURE AND SEAL BY THE ENGINEER OF RECORD. | | | | | | 3) PROVIDE A DRAWING INDICATING THE LOCATION OF THE | | | CONDENSER ON THE ROOF WITH REQUIRED CLEARANCE DUISTANCE | | | JMEASUREMENTS TO THE ROOF EDGES- SEE SECTION 304.11 | | | FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|