| Plan Review Notes For Permit 16110980 |
| Permit Number |
16110980 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-07 16:18:54 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] THE APPLICABLE CODES SHALL APPEAR ON THE DRAWINGS, | | | SPECIFY WHICH EDITION OF THE NEC THE SOLAR SYSTEM WAS | | | DESIGNED TOO MEET. FBC 107 | | | | | | 2] PLEASE SIZE OUTPUT CONDUCTORS AT 125% PER NEC 690. | | | (VERIFY WIRE SIZE FROM INVERTER OUTPUT TO | | | INTERCONNECTION POINT) | | | | | | 3] CLARIFY AIC RATING OF DISCONNECT SWITCH TO MATCH | | | EXISTING FIELD CONDITIONS. NEC 110.9 & 110.10 | | | | | | 4] IF THE SOLAR SYSTEM IS BEING TAP OFF THE LINE SIDE | | | OF THE SERVICE THE DISCONNECT SHALL BE SE RATED IN | | | ADDITION TO BEING LISTED FOR SOLAR APPLICATIONS & THE | | | NUETRAL SHALL BE BONDED TO THE CASE. NEC 230 & 250. | | | | | | 5] IF ANY QUESTIONS PLEASE CONTACT ME, KEEP IN MIND NEW | | | COMMENTS MAY BE NOTED UPON RESUBMITTAL. |
|