| 2016-12-05 13:43:21 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE GFCI RECEPTACLE OUTLET LOCATIONS ON THE | | | KITCHEN LAYOUT TO VERIFY COUNTER-TOP SPACING | | | REQUIREMENTS. FBC-R SECTIONS E3901.2.4 & E3902.6. | | | | | | 2] A MINIMUM OF 2 SMALL APPLIANCE CIRCUITS SHALL SERVE | | | THE KITCHEN COUNTER-TOP RECEPTACLE OUTLETS IN | | | ACCORDANCE WITH FBC-R SECTION E3901.3. A NOTE WILL | | | SUFFICE | | | | | | 3] PROVIDE A GFCI RECEPTACLE OUTLET WITHIN 3' OF THE | | | SINK IN BATHROOM LAYOUT PER FBC-R SECTION E3901.6. | | | | | | 4] THE BATHROOM SHALL BE FED WITH A MINIMUM 20 AMPERE | | | BRANCH CIRCUIT PER FBC SECTION E3703.4. A NOTE WILL | | | SUFFICE. | | | | | | 5] SMOKE ALARMS REQUIRED IN ACCORDANCE WITH FBC-R | | | SECTIONS 314 & 315, IF EXISTING ADD A BLOCK NOTE. | | | | | | 6] ALL NEW RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT | | | PER FBC-R SECTION E4002.14. ADD A BLOCK NOTE. | | | | | | 7] THE SCOPE OF THE WORK, JOB ADDRESS & APPLICABLE CODE | | | SHALL APPEAR ON THE DRAWING ALONG WITH THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. WPB | | | CITY AMENDMENTS 107.2.1 |
|