Plan Review Notes
Plan Review Notes For Permit 16110959
Permit Number 16110959
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-05 13:43:211ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE GFCI RECEPTACLE OUTLET LOCATIONS ON THE
 KITCHEN LAYOUT TO VERIFY COUNTER-TOP SPACING
 REQUIREMENTS. FBC-R SECTIONS E3901.2.4 & E3902.6.
  
 2] A MINIMUM OF 2 SMALL APPLIANCE CIRCUITS SHALL SERVE
 THE KITCHEN COUNTER-TOP RECEPTACLE OUTLETS IN
 ACCORDANCE WITH FBC-R SECTION E3901.3. A NOTE WILL
 SUFFICE
  
 3] PROVIDE A GFCI RECEPTACLE OUTLET WITHIN 3' OF THE
 SINK IN BATHROOM LAYOUT PER FBC-R SECTION E3901.6.
  
 4] THE BATHROOM SHALL BE FED WITH A MINIMUM 20 AMPERE
 BRANCH CIRCUIT PER FBC SECTION E3703.4. A NOTE WILL
 SUFFICE.
  
 5] SMOKE ALARMS REQUIRED IN ACCORDANCE WITH FBC-R
 SECTIONS 314 & 315, IF EXISTING ADD A BLOCK NOTE.
  
 6] ALL NEW RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
 PER FBC-R SECTION E4002.14. ADD A BLOCK NOTE.
  
 7] THE SCOPE OF THE WORK, JOB ADDRESS & APPLICABLE CODE
 SHALL APPEAR ON THE DRAWING ALONG WITH THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 CITY AMENDMENTS 107.2.1