| Plan Review Notes For Permit 16110914 |
| Permit Number |
16110914 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-05 18:18:55 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PLEASE PROVIDE ELECTRICAL PLANS WITH ALL ELECTRICAL | | | OUTLETS SHOWN, DOCUMENTS MUST BE SUBMITTED IN SETS OF 2 | | | OR MORE PER APPLICATION . FBC 107 | | | | | | 2] SHOW GFCI PROTECTION FOR GARAGE RECEPTACLES PER NEC | | | 210.8(A)(2). | | | | | | 3] IF MORE THAN A SINGLE BRANCH OR MULTI-BRANCH CIRCUIT | | | IS BEING SUPPLIED FOR POWER A GROUNDING ELECTRODE | | | SYSTEM SHALL BE INSTALLED AND CONNECTED TO THE | | | EQUIPMENT GROUNDING CONDUCTOR. NEC 250.32 (SEPERATE | | | STRUCTURE) | | | | | | | | | |
|