| 2016-12-13 13:33:48 | MECHANICAL PROVISOS | | | | | | IN AN EFFORT TO HELP EXPEDITE THE FIELD INSPECTIONS, | | | THE PROPOSED PLANS ARE APPROVED, HOWEVER A REVISION | | | WILL BE REQUIRED TO ORGANIZE THE PLANS, AND CORRECT | | | DEFICIENCIES AND CONFLICTS BETWEEN THE SUBMITTED | | | CAPTIVEAIRE SCHEDULES AND PLANS, AND THE MAIN BALL PARK | | | MECHANICAL PLANS. | | | | | | AN EXAMPLE IS LISTED BELOW: | | | 1) HOOD #1 (TAG-33) | | | THE CAPTIVEAIRE SCHEDULE IS LISTING THE SUPPLY AIR AT | | | 2005 CFMS, HOWEVER THE PLAN IS SPECIFYING MUA-S-3-3 AT | | | 3600 CFMS. | | | | | | PLEASE PROVIDE AT TIME OF INSPECTION: | | | | | | 1) THE CORRECTED PLANS AND SCHEDULES. | | | 2) A HOOD SUMMARY SHEET LISTING THE HOOD NUMBER, HOOD | | | LOCATION, AND THE CORRELATING PLAN SHEETS THAT SHOW THE | | | DUCT LAYOUTS AND DETAILS, THE FAN SCHEDULES, AND THE | | | FAN LOCATIONS. | | | 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE SELKIRK GREASE DUCT. | | | 4) WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | | ROOFTOP FANS, CURBS, AND MUA'S. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|