Plan Review Notes
Plan Review Notes For Permit 16110862
Permit Number 16110862
Review Stop M
Sequence Number 1
Notes
Date Text
2016-12-01 15:53:581ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110862
 12/1/16
  
 1) BECAUSE OF THE LACK OF GREASE DUCT AND FAN
 INFORMATION I AM NOT ABLE TO PERFORM A COMPLETE REVIEW
 ON THE SYSTEMS AS REQUIRED BY THE FLORIDA MECHANICAL
 CODE.
  
 THE LACK OF THESE DETAILS AND SPECIFICATIONS WILL ALSO
 RESULT IN FAILED INSPECTIONS IN THE FIELD.
  
 THEREFORE, IN ORDER TO APPROVE EACH PERMIT FOR THE
 HOODS (#16110858- ASTROS, & 16110861- NATIONALS) PLEASE
 ADD THE THE GREASE DUCT DETAILS AND THE MUA AND EXHAUST
 FAN INFORMATION AND SCHEDULES FOR EACH HOOD. IF THIS
 MEANS SUBMITTING THE CORRELATING PLAN SHEETS FROM THE
 MAIN
  
 PLANS THAT WOULD BE ACCEPTABLE, BUT PLEASE HIGHLIGHT
 THE ALL CORRELATING DETAILS AND EQUIPMENT SCHEDULES.
  
 TYPICAL PLAN DETAILS INCLUDE DUCT SPECIFICATIONS- TYPE
 AND GAUGE OF DUCTS, DUCT SIZES, DUCT RUNS, CLEAN-OUT
 LOCATIONS, CLEARANCES TO COMBUSTIBLES, CONNECTION AND
 SUPPORT DETAILS, VELOCITY CALCULATIONS, EXHAUST OUTLET
 AND AIR INLET LOCATIONS AND CLEARANCES.
  
 PLEASE SEE SECTION 506.
  
 ADDITIONALLY, IT WOULD BE VERY HELPFUL IF INDIVIDUAL
 HOODS SHOWN ON THE CAPTIVEAIRE PLAN SHEET NO. 1 WERE
 IDENTIFIED AS ASTROS OR NATIONALS. THIS SHEET HAS BEEN
 SUBMITTED FOR BOTH THE ASTROS AND NATIONALS PERMITS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  