| Plan Review Notes For Permit 16110835 |
| Permit Number |
16110835 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-02 17:30:13 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16110835 | | | 12/2/16 | | | | | | 1) REFER THE FBC-14 EXISTING BUILDING CODE AND PROVIDE | | | THE CLASSIFICATION OF WORK ON THE PLAN AS DETERMINED IN | | | ACCORDANCE WITH CHAPTER 5 | | | | | | 2) EXHAUST VENTILATION IS REQUIRED FOR THE TOILET ROOM | | | AND THE KITCHEN- SEE TABLE 403.3 AND SHOW COMPLIANCE. | | | | | | 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN | | | EXHAUST HOODS, FIRE SUPRESSION, AND WALK-IN COOLERS AND | | | FREEZERS. | | | | | | 4) THE PLAN IS INDICATING NATURAL VENTILATION. PLEASE | | | SEE SECTION 402.2 AND PROVIDE A CALCULATION. | | | | | | 5) REFER TO SECTION 309.1 TEMPERATURE CONTROL- AN | | | ACTIVE OR PASSIVE SPACE HEATING SYSTEM CAPABLE OF | | | MAINTAINING A MINIMUM INDOOR TEMPERATURE OF 68 DEGREES | | | IS REQUIRED. PLEASE NOTE THAT NEW CONDITIONING OF THE | | | SPACE WILL REQUIRE AC AND ENERGY CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|