Plan Review Notes
Plan Review Notes For Permit 16110820
Permit Number 16110820
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-11-22 13:15:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE HYDRALIC CALCULATIONS DO NOT APPEAR TO MEET THE
 FOLLOWING REQUIREMENTS OF NFPA 13D.
  
 CHAPTER 6 WATER SUPPLY
 6.2* WATER SUPPLY SOURCES.
 6.2.3* WHERE MORE THAN ONE DWELLING UNIT IS SERVED BY
 THE SAME WATER SUPPLY PIPE, EACH DWELLING UNIT SHALL
 HAVE AN INDIVIDUAL CONTROL VALVE THAT SERVES THE FIRE
 SPRINKLER SYSTEM IN THAT DWELLING UNIT AND THE OWNER
 SHALL HAVE ACCESS TO THE VALVE THAT CONTROLS THE
 SPRINKLER SYSTEM IN THEIR UNIT.
  
  
 CHAPTER 8 SYSTEM DESIGN
 8.1 DESIGN CRITERIA.
 8.1.1 DESIGN DISCHARGE.
 8.1.1.1 SPRINKLERS THAT ARE NOT LISTED WITH SPECIFIC
 DISCHARGE CRITERIA.
 (AREA 2) 8.1.1.1.1 THE SYSTEM SHALL PROVIDE A DISCHARGE
 OF NOT LESS THAN 13 GPM (49 L/MIN) PER SPRINKLER
 SIMULTANEOUSLY TO ALL OF THE DESIGN SPRINKLERS.( AREA
 2)
 8.1.1.1.2 THE SYSTEM SHALL PROVIDE A DISCHARGE OF NOT
 LESS THAN 18 GPM (68 L/MIN) TO ANY SPRINKLER IN THE
 SYSTEM. (BOTH AREAS)
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved