Plan Review Notes For Permit 16110817
Permit Number 16110817
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2017-02-27 11:20:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE REMIANS INSUFFICIENT DETAIL IN ENSURING THE
 RATING OF THE STAIRWELL IS MAINTAINED.
  
 DRILLING A HOLE AND APPLYING FIRE CAULK IS
 INSUFFICIENT.
  
 WHAT RATED LISTING ARE YOU USING?
  
 1) PROVIDE THE APPLICABLE RATED LISTING (I.E, UL) FOR
 THE PROPOSED 3/8" DRILL HOLE AND MOUNTING OF THE
 METALIC BOX TO THE WALL.
  
 BE SURE IT INCLUDES THE APPLICABLE FIRE CAULK TYPE.
  
 BE SURE TO INCLUDE BOTH SIDES OF THE WALL.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  