| Plan Review Notes For Permit 16110817 |
| Permit Number |
16110817 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-02-27 11:20:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE REMIANS INSUFFICIENT DETAIL IN ENSURING THE | | | RATING OF THE STAIRWELL IS MAINTAINED. | | | | | | DRILLING A HOLE AND APPLYING FIRE CAULK IS | | | INSUFFICIENT. | | | | | | WHAT RATED LISTING ARE YOU USING? | | | | | | 1) PROVIDE THE APPLICABLE RATED LISTING (I.E, UL) FOR | | | THE PROPOSED 3/8" DRILL HOLE AND MOUNTING OF THE | | | METALIC BOX TO THE WALL. | | | | | | BE SURE IT INCLUDES THE APPLICABLE FIRE CAULK TYPE. | | | | | | BE SURE TO INCLUDE BOTH SIDES OF THE WALL. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|