| Notes |
| Date |
Text |
| 2016-12-01 11:33:25 | 525 OKEECHOBEE BOULEVARD #970 | | | PERMIT #16110817 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | CARD READERS ARE NOT PERMITTED IN THE PROTECTED EXIT | | | STAIRS. PER SECTION FFPC (NFPA 101) 7.1.3.2.1, | | | PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES | | | FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED | | | EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT | | | ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING | | | NECESSARY FOR THE HEATING OR COOLING OF THE EXIT | | | ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND | | | PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE | | | CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE | | | PENETRATIONS ARE PROTECTED. | | | | | | HOW ARE THE STAIRWELL RE-ENTRY REQUIREMENTS OF THE | | | BUILDING BEING ACCOMPLISHED IN ACCORDANCE WITH NFPA | | | 101? | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|