| 2016-12-20 12:31:45 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | PROVIDE A SUMMARY LOAD CALCULATION FOR THE SELECTION |
| | AND SIZING OF THE ELECTRICAL SERVICE AS NOTED WITHIN |
| | THE NEC. CONTINUOUS LOADS SUCH AS AC SHOULD BE INCLUDED |
| | AT 100%. NEC 220.4, 220.80 |
| | |
| | INTERCONNECTED SMOKE ALARMS ARE REQUIRED BOTH WITHIN |
| | AND OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| | |
| | THE ELECTRIC SUBPANEL AT THE GUEST HOUSE MAY NOT BE |
| | LOCATED IN A CLOSET. PANELS SHALL BE PLACED SO AS TO |
| | REDUCE TO A MINIMUM THE PROBABILITY OF COMMUNICATING |
| | FIRE TO ADJACENT COMBUSTIBLE MATERIALS. OVERCURRENT |
| | DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY |
| | IGNITABLE MATERIAL. SUFFICIENT ACCESS AND WORKING SPACE |
| | IS REQUIRED AT THE SUB PANEL. 36"X 30? IN WIDTH IS THE |
| | MINIMUM REQUIRED FOR SUB PANELS. NEC 408.17, 240.24 |
| | (D), 110.26 (A) |
| | |
| | CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE |
| | LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9 |
| | |
| | HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES |
| | NEED TO BE RATED FOR INSULATION CONTACT. NEC 410.116; |
| | FBC R 4004 |
| | |
| | SWIMMING POOL PUMPS AND SPA EQUIPMENT MUST BE GFCI |
| | PROTECTED. NEC 680.21(C), FBC R E4203.1.3 |
| | |
| | PROVIDE SAFE WORKING CLEARANCES FOR ALL OUTSIDE AIR |
| | CONDITIONING UNIT DISCONNECTS. NEC 110.26, FBC E3405.1 |
| | |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94; FBC R E3609 |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |