| Notes |
| Date |
Text |
| 2016-11-28 09:14:58 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | 1] A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS | | | SHALL BE PROVIDED TO SERVE ALL WALL AND FLOOR | | | RECEPTACLE OUTLETS LOCATED IN THE KITCHEN. NEC | | | 210.52(B)(1) A NOTE WILL SUFFICE. | | | | | | 2] SHOW GFCI PROTECTED RECEPTACLE OUTLETS & COMPLY WITH | | | COUNTER TOP SPACING REQUIREMENTS ON THE KITCHEN LAYOUT | | | FLOOR PLAN, INCLUDE ALL KITCHEN APPLIANCES OUTLET | | | LOCATION (RANGE,DISHWASHER,MICROWAVE, & ETC) ASWELL PER | | | NEC 210.8(A)(6) & 210.52(C) | | | | | | |
|