2016-12-22 08:03:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FOUNDATION NOTE #3 ON SHEET A2.2 STATES THAT THE
 SOIL IS ASSUMBED TO BE CAPABLE OF SUPPORTING 2,500 PSF.
 THE SOIL REPORT IS FOR A NET ALLOWABLE SOIL BEARING
 CAPACITY OF 1500 PSF. FOUNDATION NOTE #3 ON SHEET A1.3
 SPECIFIES A REQUIRED SOIL BEARING CAPACITY OF 1500 PSF.
 PLEASE REVIEW AND CORRECT. FBC-R401.2
  
 2) THERE IS A CONFLICT WITH THE EXPOSURE CATEGORIES
 THAT ARE SPECIFIED ON THE PLANS. PLAN SHEET A2.2
 SPECIFES EXPOSURE C AND SHEET A1.3 SPECIFIES EXPOSURE D
 UNDER CODES AND STANDARDS NOTE #1. THE TRUSS DRAWINGS
 ARE FOR EXPOSURE C. PLEASE REVIEW AND CORRECT.
 FBC-R301.2.1.4
  
 3) ON SHEET A1.2 GENERAL NOTE 1 REFERENCES MARTIN
 COUNTY AMENDMENTS. THIS PROJECT IS LOCATED WITHIN THE
 CITY OF WEST PALM BEACH'S JURISDICTION. THEREFORE, THE
 CITY OF WEST PALM BEACH'S AMENDMENTS SHALL APPLY. FBC
 CHAPTER 1.
  
 4) ON SHEET A1.3 THE WRONG EDITION OF ACI 530, 530.1,
 ASCE 5, 6 AND TMS402, 602 IS SPECIFIED. THE 2014 FBCR
 REFERENCES THE 2011 EDITIONS OF THESE STANDARDS.
  
 5) TYPICAL ROOF NOTE A ON A2.2 SPECIFIES 8D RING SHANK
 NAILS. THE NAILING ROOF SHEATHING TABLE HAS 10D RING
 SHANK NAILS FOR ROOF ZONE 3. ON SHEET A2.3 10D RING
 SHANK NAILS ARE SPECIFIED. PLEASE REVIEW AND CORRECT.
 FBC-R803.2.3.1
  
 6) THE TRUSS PLANS INDICATE THAT THE LOWER 10:12 SLOPE
 ROOF OVER THE FIRST FLOOR WINDOW SEAT WILL BE FRAMED BY
 THE BUILDER. PROVIDE FRAMING DETAILS FOR THIS ROOF ON
 THE PLANS. FBC 107.2.1
  
 7) SHOW COMPLIANCE WITH THE FOLLOWING :
 - FBC-R806.1 VENTILATION REQUIRED. ENCLOSED ATTICS AND
 ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL
 HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN OR SNOW. VENTILATION OPENINGS SHALL HAVE A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A LEAST
 DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS
 HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING
 MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 R802.1.8. REQUIRED VENTILATION OPENINGS SHALL OPEN
 DIRECTLY TO THE OUTSIDE AIR.
 - R806.2 MINIMUM VENT AREA. THE MINIMUM NET FREE
 VENTILATING AREA SHALL BE 1/150 OF THE AREA OF THE
 VENTED SPACE.
  
 8) SPECIFY THE R-VALUES OF THE WALL AND CEILING
 INSULATION ON THE PLANS. FBC 107.2.1
  
 9) PROVIDE STAIR GUARDRAIL DETAILS TO SHOW COMPLIANCE
 WITH THE FOLLOWING:
 - FBC-R R301.5 LIVE LOAD. THE MINIMUM UNIFORMLY
 DISTRIBUTED LIVE LOAD SHALL BE AS PROVIDED IN TABLE
 R301.5. A 200 PSF LIVE LOAD APPLIED IN ANY DIRECTION AT
 ANY POINT ALONG THE TOP. GUARD IN-FILL COMPONENTS (ALL
 THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS
 SHALL BE DESIGNED TO WITHSTAND A HORIZONTALLY APPLIED
 NORMAL LOAD OF 50 POUNDS ON AN AREA EQUAL TO 1 SQUARE
 FOOT. THIS LOAD NEED NOT BE ASSUMED TO ACT CONCURRENTLY
 WITH ANY OTHER LIVE LOAD REQUIREMENT.
  
 10) SHOW COMPLIANCE WITH FBC-R302.11 FIREBLOCKING SHALL
 BE PROVIDED IN WOOD-FRAME CONSTRUCTION IN THE FOLLOWING
 LOCATIONS: (3) IN CONCEALED SPACES BETWEEN STAIR
 STRINGERS AT THE TOP AND BOTTOM OF THE RUN. ENCLOSED
 SPACES UNDER STAIRS SHALL COMPLY WITH SECTION R302.7.
  
 11) ON SHEET A.7.1 THE PLANS SPECIFY WOOD WINDOWS AND
 THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 ALUMINUM WINDOWS. PLEASE CLARIFY. FBC 107.2.1
  
 12) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE LARGE
 MISSILE IMPACT RATED FIXED WINDOWS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. FBC
 107.3.4.1
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  