| Plan Review Notes For Permit 16110752 |
| Permit Number |
16110752 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-17 08:31:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF A SIGNED AND SEALED FASTENER PULL | | | TEST FOR THE STEEL DECK IN ACCORDANCE WITH TAS 105 TO | | | VERIFY THAT THE FASTENER PULL OUT VALUE IS EQUAL OR | | | GREATER THAN THE -210 LBF THAT WAS USED IN THE RAS 117 | | | CALCULATIONS. FBC 107.2.1.3 |
|